Lamma Power Station Extension - Air Quality Monitoring Data for Unit L9 (Operation)
Month: March 2009
Date Daily Maximum Stack NOx Concentration
¡@ (mg/Nm3)#
1/3/2009 56
2/3/2009 59
3/3/2009 59
4/3/2009 60
5/3/2009 58
6/3/2009 59
7/3/2009 58
8/3/2009 62
9/3/2009 62
10/3/2009 60
11/3/2009 58
12/3/2009 57
13/3/2009 52
14/3/2009 68
15/3/2009 62
16/3/2009 57
17/3/2009 57
18/3/2009 55
19/3/2009 54
20/3/2009 52
21/3/2009 50
22/3/2009 45
23/3/2009 51
24/3/2009 53
25/3/2009 56
26/3/2009 63
27/3/2009 58
28/3/2009 55
29/3/2009 59
30/3/2009 59
31/3/2009 60
Note: # - Hourly average value.  Expressed as at 0ºC, 101.325kPa, dry and
               corrected to 15% O2 condition.