Lamma Power Station Extension - Air Quality Monitoring Data for Unit L9 (Operation)
Month: January 2011
Date Daily Maximum Stack NOx Concentration
¡@ (mg/Nm3)#
1/1/2011 76
2/1/2011 74
3/1/2011 75
4/1/2011 74
5/1/2011 73
6/1/2011 76
7/1/2011 78
8/1/2011 73
9/1/2011 72
10/1/2011 78
11/1/2011 78
12/1/2011 76
13/1/2011 77
14/1/2011 77
15/1/2011 76
16/1/2011 78
17/1/2011 77
18/1/2011 76
19/1/2011 74
20/1/2011 73
21/1/2011 75
22/1/2011 *
23/1/2011 *
24/1/2011 *
25/1/2011 *
26/1/2011 *
27/1/2011 *
28/1/2011 *
29/1/2011 *
30/1/2011 *
31/1/2011 *
Note: # - Hourly average value.  Expressed as at 0ºC, 101.325kPa, dry and
               corrected to 15% O2 condition.
         * - Unit L9 was not on load.