Lamma Power Station Extension - Air Quality Monitoring Data for Unit L9 (Operation)
Month: July 2012
Date Daily Maximum Stack NOx Concentration
¡@ (mg/Nm3)#
1/7/2012 58
2/7/2012 55
3/7/2012 55
4/7/2012 54
5/7/2012 54
6/7/2012 55
7/7/2012 54
8/7/2012 55
9/7/2012 53
10/7/2012 54
11/7/2012 53
12/7/2012 53
13/7/2012 53
14/7/2012 53
15/7/2012 48
16/7/2012 52
17/7/2012 52
18/7/2012 52
19/7/2012 55
20/7/2012 52
21/7/2012 52
22/7/2012 55
23/7/2012 55
24/7/2012 52
25/7/2012 55
26/7/2012 56
27/7/2012 54
28/7/2012 *
29/7/2012 54
30/7/2012 55
31/7/2012 53
Note: # - Hourly average value.  Expressed as at 0ºC, 101.325kPa, dry and
               corrected to 15% O2 condition.
         * - Unit L9 was not on load.