Lamma Power Station Extension - Air Quality Monitoring Data for unit L10/L11 (Construction)

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

4/8/2020

13

21

11

13

4/8/2020

15:00 - 15:59

12

36

8

10/8/2020

15

17

10

14

16:00 - 16:59

15

31

9

16/8/2020

15

19

13

11

17:00 - 17:59

16

26

8

22/8/2020

34

50

35

21

10/8/2020

15:00 - 15:59

23

13

10

28/8/2020

30

34

25

29

16:00 - 16:59

17

12

10

 

 

 

 

 

17:00 - 17:59

22

5

9

 

 

 

 

 

16/8/2020

15:00 - 15:59

14

16

14

 

 

 

 

 

16:00 - 16:59

17

19

15

 

 

 

 

 

17:00 - 17:59

19

25

17

 

 

 

 

 

22/8/2020

15:00 - 15:59

23

54

24

16:00 - 16:59

20

60

23

17:00 - 17:59

29

65

23

 

 

 

 

 

 

28/8/2020

15:00 - 15:59

45

51

29

 

 

 

 

 

 

16:00 - 16:59

36

35

25

 

 

 

 

 

 

17:00 - 17:59

21

28

24

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/8/2020

47

 

2/8/2020

45

 

3/8/2020

46

 

4/8/2020

46

 

5/8/2020

45

 

6/8/2020

48

 

7/8/2020

48

 

8/8/2020

47

 

9/8/2020

47

 

10/8/2020

46

 

11/8/2020

44

 

12/8/2020

46

 

13/8/2020

47

 

14/8/2020

*

 

15/8/2020

40

 

16/8/2020

48

 

17/8/2020

46

 

18/8/2020

48

 

19/8/2020

47

 

20/8/2020

46

 

21/8/2020

47

 

22/8/2020

 

46

 

23/8/2020

 

48

 

24/8/2020

 

45

 

25/8/2020

 

44

 

26/8/2020

 

45

 

27/8/2020

 

47

 

28/8/2020

 

45

 

29/8/2020

 

45

 

30/8/2020

 

46

 

 

 

 

 

 

 

 

31/8/2020

 

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

# - Hourly average value.  Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L9 was not on load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/8/2020

 

3

 

2/8/2020

 

3

 

3/8/2020

 

3

 

4/8/2020

 

*

 

5/8/2020

 

3

 

 

 

 

 

 

 

 

6/8/2020

 

3

 

7/8/2020

 

3

 

8/8/2020

 

3

 

9/8/2020

 

3

 

10/8/2020

 

3

 

11/8/2020

 

3

 

12/8/2020

 

3

 

13/8/2020

 

3

 

14/8/2020

 

3

 

15/8/2020

 

3

 

16/8/2020

 

3

 

17/8/2020

 

3

 

18/8/2020

 

3

 

19/8/2020

 

3

 

20/8/2020

 

3

 

21/8/2020

 

3

 

22/8/2020

 

3

 

23/8/2020

 

3

 

24/8/2020

 

3

 

25/8/2020

 

3

 

26/8/2020

 

3

 

 

 

 

 

 

 

 

27/8/2020

 

3

 

28/8/2020

 

3

 

29/8/2020

 

3

 

30/8/2020

 

3

 

31/8/2020

 

3

 

 

 

 

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L10 was not on load.