Lamma
Power Station Extension - Air Quality Monitoring Data for unit L10/L11
(Construction) |
||||||||||
24-hr
TSP (µg/m3) |
1-hr
TSP (µg/m3) |
|||||||||
Date |
Reservoir (AM1) |
East
Gate (AM2) |
Ash
Lagoon (AM3) |
Tai
Yuen Village (AM4) |
Date |
Time |
Reservoir
(AM1) |
East
Gate (AM2) |
Ash
Lagoon (AM3) |
|
2/11/2020 |
56 |
69 |
54 |
46 |
2/11/2020 |
15:00 - 15:59 |
77 |
106 |
62 |
|
8/11/2020 |
63 |
69 |
62 |
57 |
16:00 - 16:59 |
70 |
90 |
66 |
||
14/11/2020 |
44 |
55 |
40 |
25 |
17:00 - 17:59 |
74 |
76 |
65 |
||
20/11/2020 |
22 |
24 |
14 |
29 |
8/11/2020 |
15:00 - 15:59 |
71 |
64 |
52 |
|
26/11/2020 |
47 |
48 |
36 |
51 |
16:00 - 16:59 |
44 |
69 |
60 |
||
|
|
|
|
|
17:00 - 17:59 |
72 |
78 |
68 |
||
|
|
|
|
|
14/11/2020 |
15:00 - 15:59 |
66 |
98 |
75 |
|
|
|
|
|
|
16:00 - 16:59 |
73 |
64 |
38 |
||
|
|
|
|
|
17:00 - 17:59 |
62 |
62 |
38 |
||
|
|
|
|
|
20/11/2020 |
15:00 - 15:59 |
22 |
19 |
16 |
|
16:00 - 16:59 |
24 |
21 |
15 |
|||||||
17:00 - 17:59 |
15 |
22 |
14 |
|||||||
|
|
|
|
|
|
26/11/2020 |
15:00 - 15:59 |
63 |
55 |
44 |
|
|
|
|
|
|
16:00 - 16:59 |
59 |
53 |
42 |
|
|
|
|
|
|
|
17:00 - 17:59 |
55 |
51 |
40 |
|
|
||||||||||
Lamma
Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation) |
||||||||||
Date |
Daily
Maximum Stack NOx concentration (mg/Nm3)# |
|||||||||
1/11/2020 |
57 |
|||||||||
2/11/2020 |
56 |
|||||||||
3/11/2020 |
55 |
|||||||||
4/11/2020 |
57 |
|||||||||
5/11/2020 |
56 |
|||||||||
6/11/2020 |
54 |
|||||||||
7/11/2020 |
56 |
|||||||||
8/11/2020 |
57 |
|||||||||
9/11/2020 |
59 |
|||||||||
10/11/2020 |
59 |
|||||||||
11/11/2020 |
56 |
|||||||||
12/11/2020 |
62 |
|||||||||
13/11/2020 |
59 |
|||||||||
14/11/2020 |
59 |
|||||||||
15/11/2020 |
54 |
|||||||||
16/11/2020 |
56 |
|||||||||
17/11/2020 |
54 |
|||||||||
18/11/2020 |
53 |
|||||||||
19/11/2020 |
52 |
|||||||||
20/11/2020 |
53 |
|||||||||
21/11/2020 |
54 |
|||||||||
22/11/2020 |
56 |
|||||||||
23/11/2020 |
53 |
|||||||||
24/11/2020 |
56 |
|||||||||
25/11/2020 |
57 |
|||||||||
26/11/2020 |
56 |
|||||||||
27/11/2020 |
57 |
|||||||||
28/11/2020 |
56 |
|||||||||
29/11/2020 |
57 |
|||||||||
30/11/2020 |
58 |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
Note: |
|
|
|
|
|
|||||
# - Hourly average value.
Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition. |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
Lamma Power
Station Extension - Air Quality Monitoring Data for unit L10 (Operation) |
||||||||||
Date |
Daily
Maximum Stack NOx concentration (mg/Nm3)# |
|||||||||
1/11/2020 |
|
3 |
|
|||||||
2/11/2020 |
|
3 |
|
|||||||
3/11/2020 |
|
3 |
|
|||||||
4/11/2020 |
|
3 |
|
|||||||
5/11/2020 |
|
3 |
|
|
|
|
|
|
|
|
6/11/2020 |
|
3 |
|
|||||||
7/11/2020 |
|
3 |
|
|||||||
8/11/2020 |
|
3 |
|
|||||||
9/11/2020 |
|
3 |
|
|||||||
10/11/2020 |
|
3 |
|
|||||||
11/11/2020 |
|
3 |
|
|||||||
12/11/2020 |
|
3 |
|
|||||||
13/11/2020 |
|
3 |
|
|||||||
14/11/2020 |
|
3 |
|
|||||||
15/11/2020 |
|
3 |
|
|||||||
16/11/2020 |
|
3 |
|
|||||||
17/11/2020 |
|
3 |
|
|||||||
18/11/2020 |
|
3 |
|
|||||||
19/11/2020 |
|
3 |
|
|||||||
20/11/2020 |
|
3 |
|
|||||||
21/11/2020 |
|
3 |
|
|||||||
22/11/2020 |
|
3 |
|
|||||||
23/11/2020 |
|
3 |
|
|||||||
24/11/2020 |
|
3 |
|
|||||||
25/11/2020 |
|
3 |
|
|||||||
26/11/2020 |
|
3 |
|
|
|
|
|
|
|
|
27/11/2020 |
|
3 |
|
|||||||
28/11/2020 |
|
3 |
|
|||||||
29/11/2020 |
|
* |
|
|||||||
30/11/2020 |
|
* |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The
daily maximum stack NOx concentration complies with the Action/Limit Level
for all unit loading ranges. Note: # - Hourly average value.
Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition. * - Unit L10 was