Lamma Power Station Extension - Air Quality Monitoring Data for unit L10/L11 (Construction)

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

6/5/2021

47

49

40

31

6/5/2021

15:00 - 15:59

41

42

33

12/5/2021

22

24

15

31

16:00 - 16:59

47

44

36

18/5/2021

30

37

16

21

17:00 - 17:59

46

44

37

24/5/2021

16

17

12

29

12/5/2021

15:00 - 15:59

20

27

12

30/5/2021

33

42

22

17

16:00 - 16:59

19

30

15

 

 

 

 

 

17:00 - 17:59

24

28

15

 

 

 

 

 

18/5/2021

15:00 - 15:59

24

82

29

 

 

 

 

 

16:00 - 16:59

34

101

22

 

 

 

 

 

17:00 - 17:59

64

107

19

 

 

 

 

 

24/5/2021

15:00 - 15:59

21

20

15

16:00 - 16:59

30

20

15

17:00 - 17:59

15

18

14

 

 

 

 

 

 

30/5/2021

15:00 - 15:59

30

64

23

 

 

 

 

 

 

16:00 - 16:59

32

55

24

 

 

 

 

 

 

17:00 - 17:59

36

46

23

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/5/2021

49

2/5/2021

54

3/5/2021

52

4/5/2021

52

5/5/2021

51

6/5/2021

52

7/5/2021

52

8/5/2021

49

9/5/2021

49

10/5/2021

51

11/5/2021

48

12/5/2021

47

13/5/2021

47

14/5/2021

48

15/5/2021

52

16/5/2021

52

17/5/2021

51

18/5/2021

51

19/5/2021

52

20/5/2021

52

21/5/2021

51

22/5/2021

51

23/5/2021

50

24/5/2021

50

25/5/2021

51

26/5/2021

52

 

 

 

 

 

 

 

27/5/2021

50

 

 

 

 

 

 

 

28/5/2021

50

 

 

 

 

 

 

 

29/5/2021

49

 

 

 

 

 

 

 

30/5/2021

48

31/5/2021

47

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

# - Hourly average value.  Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/5/2021

 

3

 

2/5/2021

 

3

 

3/5/2021

 

3

 

4/5/2021

 

3

 

5/5/2021

 

3

 

 

 

 

 

 

 

 

6/5/2021

 

3

 

7/5/2021

 

3

 

8/5/2021

 

3

 

9/5/2021

 

3

 

10/5/2021

 

3

 

11/5/2021

 

3

 

12/5/2021

 

3

 

13/5/2021

 

3

 

14/5/2021

 

3

 

15/5/2021

 

3

 

16/5/2021

 

3

 

17/5/2021

 

3

 

18/5/2021

 

3

 

19/5/2021

 

3

 

20/5/2021

 

3

 

21/5/2021

 

3

 

22/5/2021

 

3

 

23/5/2021

 

3

 

24/5/2021

 

3

 

25/5/2021

 

3

 

 

 

 

 

 

 

 

26/5/2021

 

3

 

 

 

 

 

 

 

 

27/5/2021

 

3

 

 

 

 

 

 

 

 

28/5/2021

 

3

 

 

 

 

 

 

 

 

29/5/2021

 

*

 

30/5/2021

 

*

 

 

 

 

 

 

 

 

31/5/2021

 

3

 

 

 

 

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0°C, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L10 was not on load.