Lamma Power Station Extension - Air Quality Monitoring Data for unit L11/L12 (Construction)

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

6/7/2022

23

26

17

13

6/7/2022

15:00 - 15:59

22

34

15

12/7/2022

13

11

8

15

16:00 - 16:59

20

27

11

18/7/2022

36

16

21

10

17:00 - 17:59

19

25

11

24/7/2022

49

19

17

13

12/7/2022

15:00 - 15:59

4

8

7

30/7/2022

38

26

24

21

16:00 - 16:59

18

12

10

17:00 - 17:59

17

14

11

 

 

 

 

 

 

18/7/2022

15:00 - 15:59

41

13

19

 

 

 

 

 

 

16:00 - 16:59

38

14

20

 

 

 

 

 

 

17:00 - 17:59

33

15

22

 

 

 

 

 

 

24/7/2022

15:00 - 15:59

156

19

19

 

 

 

 

 

 

16:00 - 16:59

76

27

19

 

 

 

 

 

 

17:00 - 17:59

45

34

20

 

 

 

 

 

 

30/7/2022

15:00 - 15:59

32

27

38

 

 

 

 

 

 

16:00 - 16:59

46

26

36

 

 

 

 

 

 

17:00 - 17:59

51

23

38

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/7/2022

*

2/7/2022

39

3/7/2022

42

4/7/2022

42

5/7/2022

43

6/7/2022

46

7/7/2022

45

8/7/2022

47

9/7/2022

46

10/7/2022

48

11/7/2022

50

12/7/2022

49

13/7/2022

50

14/7/2022

45

15/7/2022

44

16/7/2022

43

17/7/2022

43

18/7/2022

44

19/7/2022

45

20/7/2022

45

21/7/2022

46

22/7/2022

47

23/7/2022

45

24/7/2022

45

25/7/2022

44

26/7/2022

47

 

 

 

 

 

 

 

27/7/2022

48

 

 

 

 

 

 

 

28/7/2022

46

 

 

 

 

 

 

 

29/7/2022

44

 

 

 

 

 

 

 

30/7/2022

46

 

 

 

 

 

 

 

31/7/2022

40

 

 

 

 

 

 

 

Note:

 

 

 

 

 

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

 

 

 

 

* - Unit L9 was not on load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/7/2022

3

2/7/2022

3

3/7/2022

3

4/7/2022

3

5/7/2022

3

 

 

 

 

 

 

 

6/7/2022

3

7/7/2022

3

8/7/2022

3

9/7/2022

3

10/7/2022

3

11/7/2022

3

 

 

 

 

 

 

 

12/7/2022

3

 

 

 

 

 

 

 

13/7/2022

4

 

 

 

 

 

 

 

14/7/2022

3

 

 

 

 

 

 

 

15/7/2022

3

 

 

 

 

 

 

 

16/7/2022

3

 

 

 

 

 

 

 

17/7/2022

3

 

 

 

 

 

 

 

18/7/2022

3

 

 

 

 

 

 

 

19/7/2022

3

 

 

 

 

 

 

 

20/7/2022

3

 

 

 

 

 

 

 

21/7/2022

3

 

 

 

 

 

 

 

22/7/2022

3

 

 

 

 

 

 

 

23/7/2022

3

 

 

 

 

 

 

 

24/7/2022

3

 

 

 

 

 

 

 

25/7/2022

3

 

 

 

 

 

 

 

26/7/2022

3

 

 

 

 

 

 

 

27/7/2022

3

 

 

 

 

 

 

 

28/7/2022

3

 

 

 

 

 

 

 

29/7/2022

3

 

 

 

 

 

 

 

30/7/2022

3

 

 

 

 

 

 

 

31/7/2022

3

 

 

 

 

 

 

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L10 was not on load.

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L11 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/7/2022

3

 

 

 

 

 

 

 

2/7/2022

3

 

 

 

 

 

 

 

3/7/2022

3

 

 

 

 

 

 

 

4/7/2022

2

 

 

 

 

 

 

 

5/7/2022

3

 

 

 

 

 

 

 

6/7/2022

3

 

 

 

 

 

 

 

7/7/2022

2

 

 

 

 

 

 

 

8/7/2022

3

 

 

 

 

 

 

 

9/7/2022

*

 

 

 

 

 

 

 

10/7/2022

2

 

 

 

 

 

 

 

11/7/2022

3

 

 

 

 

 

 

 

12/7/2022

3

 

 

 

 

 

 

 

13/7/2022

3

 

 

 

 

 

 

 

14/7/2022

3

 

 

 

 

 

 

 

15/7/2022

2

 

 

 

 

 

 

 

16/7/2022

2

 

 

 

 

 

 

 

17/7/2022

3

 

 

 

 

 

 

 

18/7/2022

3

 

 

 

 

 

 

 

19/7/2022

3

 

 

 

 

 

 

 

20/7/2022

3

 

 

 

 

 

 

 

21/7/2022

3

 

 

 

 

 

 

 

22/7/2022

3

 

 

 

 

 

 

 

23/7/2022

3

24/7/2022

3

25/7/2022

3

26/7/2022

3

27/7/2022

3

 

 

 

 

 

 

 

28/7/2022

3

29/7/2022

3

30/7/2022

3

 

 

 

 

 

 

 

31/7/2022

2

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L11 was not on load.