Lamma Power Station Extension - Air Quality Monitoring Data for unit L11/L12 (Construction)

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

5/8/2022

13

10

13

11

5/8/2022

15:00 - 15:59

12

7

13

11/8/2022

18

14

13

18

16:00 - 16:59

4

6

9

17/8/2022

13

9

5

13

17:00 - 17:59

6

6

7

23/8/2022

49

39

32

29

11/8/2022

15:00 - 15:59

12

11

5

29/8/2022

25

19

21

33

16:00 - 16:59

6

8

4

17:00 - 17:59

5

7

6

 

 

 

 

 

 

17/8/2022

15:00 - 15:59

18

16

10

 

 

 

 

 

 

16:00 - 16:59

20

13

10

 

 

 

 

 

 

17:00 - 17:59

10

7

7

 

 

 

 

 

 

23/8/2022

15:00 - 15:59

197

47

52

 

 

 

 

 

 

16:00 - 16:59

104

42

45

 

 

 

 

 

 

17:00 - 17:59

70

32

36

 

 

 

 

 

 

29/8/2022

15:00 - 15:59

34

17

17

 

 

 

 

 

 

16:00 - 16:59

26

22

18

 

 

 

 

 

 

17:00 - 17:59

22

22

18

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/8/2022

41

2/8/2022

40

3/8/2022

42

4/8/2022

41

5/8/2022

41

6/8/2022

40

7/8/2022

43

8/8/2022

44

9/8/2022

44

10/8/2022

41

11/8/2022

40

12/8/2022

40

13/8/2022

45

14/8/2022

41

15/8/2022

41

16/8/2022

40

17/8/2022

38

18/8/2022

39

19/8/2022

39

20/8/2022

39

21/8/2022

39

22/8/2022

39

23/8/2022

42

24/8/2022

43

25/8/2022

40

26/8/2022

38

 

 

 

 

 

 

 

27/8/2022

43

 

 

 

 

 

 

 

28/8/2022

39

 

 

 

 

 

 

 

29/8/2022

39

 

 

 

 

 

 

 

30/8/2022

39

 

 

 

 

 

 

 

31/8/2022

39

 

 

 

 

 

 

 

Note:

 

 

 

 

 

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/8/2022

3

2/8/2022

3

3/8/2022

4

4/8/2022

3

5/8/2022

3

 

 

 

 

 

 

 

6/8/2022

3

7/8/2022

3

8/8/2022

3

9/8/2022

3

10/8/2022

3

11/8/2022

3

 

 

 

 

 

 

 

12/8/2022

3

 

 

 

 

 

 

 

13/8/2022

3

 

 

 

 

 

 

 

14/8/2022

3

 

 

 

 

 

 

 

15/8/2022

3

 

 

 

 

 

 

 

16/8/2022

3

 

 

 

 

 

 

 

17/8/2022

3

 

 

 

 

 

 

 

18/8/2022

3

 

 

 

 

 

 

 

19/8/2022

3

 

 

 

 

 

 

 

20/8/2022

3

 

 

 

 

 

 

 

21/8/2022

3

 

 

 

 

 

 

 

22/8/2022

3

 

 

 

 

 

 

 

23/8/2022

3

 

 

 

 

 

 

 

24/8/2022

3

 

 

 

 

 

 

 

25/8/2022

3

 

 

 

 

 

 

 

26/8/2022

3

 

 

 

 

 

 

 

27/8/2022

3

 

 

 

 

 

 

 

28/8/2022

3

 

 

 

 

 

 

 

29/8/2022

3

 

 

 

 

 

 

 

30/8/2022

3

 

 

 

 

 

 

 

31/8/2022

3

 

 

 

 

 

 

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L11 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/8/2022

3

 

 

 

 

 

 

 

2/8/2022

3

 

 

 

 

 

 

 

3/8/2022

3

 

 

 

 

 

 

 

4/8/2022

3

 

 

 

 

 

 

 

5/8/2022

3

 

 

 

 

 

 

 

6/8/2022

3

 

 

 

 

 

 

 

7/8/2022

3

 

 

 

 

 

 

 

8/8/2022

3

 

 

 

 

 

 

 

9/8/2022

2

 

 

 

 

 

 

 

10/8/2022

2

 

 

 

 

 

 

 

11/8/2022

3

 

 

 

 

 

 

 

12/8/2022

3

 

 

 

 

 

 

 

13/8/2022

3

 

 

 

 

 

 

 

14/8/2022

2

 

 

 

 

 

 

 

15/8/2022

2

 

 

 

 

 

 

 

16/8/2022

2

 

 

 

 

 

 

 

17/8/2022

2

 

 

 

 

 

 

 

18/8/2022

2

 

 

 

 

 

 

 

19/8/2022

2

 

 

 

 

 

 

 

20/8/2022

2

 

 

 

 

 

 

 

21/8/2022

2

 

 

 

 

 

 

 

22/8/2022

3

 

 

 

 

 

 

 

23/8/2022

3

24/8/2022

2

25/8/2022

3

26/8/2022

2

27/8/2022

2

 

 

 

 

 

 

 

28/8/2022

2

29/8/2022

2

30/8/2022

2

 

 

 

 

 

 

 

31/8/2022

2

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.