Lamma Power Station Extension - Air Quality Monitoring Data for unit L11/L12 (Construction)

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

4/10/2022

34

28

27

21

4/10/2022

15:00 - 15:59

96

28

39

10/10/2022

59

80

43

42

16:00 - 16:59

118

28

37

16/10/2022

102

79

55

89

17:00 - 17:59

51

27

35

22/10/2022

44

36

43

35

10/10/2022

15:00 - 15:59

45

63

56

28/10/2022

50

38

44

43

16:00 - 16:59

59

67

86

17:00 - 17:59

59

70

79

 

 

 

 

 

 

16/10/2022

15:00 - 15:59

82

87

64

 

 

 

 

 

 

16:00 - 16:59

122

90

69

 

 

 

 

 

 

17:00 - 17:59

148

81

66

 

 

 

 

 

 

22/10/2022

15:00 - 15:59

48

41

44

 

 

 

 

 

 

16:00 - 16:59

52

38

54

 

 

 

 

 

 

17:00 - 17:59

46

42

51

 

 

 

 

 

 

28/10/2022

15:00 - 15:59

79

58

58

 

 

 

 

 

 

16:00 - 16:59

73

44

55

 

 

 

 

 

 

17:00 - 17:59

64

33

44

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/10/2022

48

2/10/2022

54

3/10/2022

51

4/10/2022

*

5/10/2022

51

6/10/2022

50

7/10/2022

52

8/10/2022

*

9/10/2022

*

10/10/2022

*

11/10/2022

*

12/10/2022

*

13/10/2022

*

14/10/2022

*

15/10/2022

*

16/10/2022

*

17/10/2022

*

18/10/2022

*

19/10/2022

*

20/10/2022

*

21/10/2022

*

22/10/2022

*

23/10/2022

57

24/10/2022

62

25/10/2022

66

26/10/2022

66

 

 

 

 

 

 

 

27/10/2022

65

 

 

 

 

 

 

 

28/10/2022

65

 

 

 

 

 

 

 

29/10/2022

54

 

 

 

 

 

 

 

30/10/2022

*

 

 

 

 

 

 

 

31/10/2022

*

 

 

 

 

 

 

 

Note:

 

 

 

 

 

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

 

 

 

 

* - Unit L9 was not on load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/10/2022

3

2/10/2022

3

3/10/2022

3

4/10/2022

3

5/10/2022

3

 

 

 

 

 

 

 

6/10/2022

3

7/10/2022

3

8/10/2022

3

9/10/2022

*

10/10/2022

3

11/10/2022

3

 

 

 

 

 

 

 

12/10/2022

3

 

 

 

 

 

 

 

13/10/2022

3

 

 

 

 

 

 

 

14/10/2022

3

 

 

 

 

 

 

 

15/10/2022

3

 

 

 

 

 

 

 

16/10/2022

3

 

 

 

 

 

 

 

17/10/2022

3

 

 

 

 

 

 

 

18/10/2022

3

 

 

 

 

 

 

 

19/10/2022

3

 

 

 

 

 

 

 

20/10/2022

3

 

 

 

 

 

 

 

21/10/2022

3

 

 

 

 

 

 

 

22/10/2022

3

 

 

 

 

 

 

 

23/10/2022

3

 

 

 

 

 

 

 

24/10/2022

3

 

 

 

 

 

 

 

25/10/2022

3

 

 

 

 

 

 

 

26/10/2022

3

 

 

 

 

 

 

 

27/10/2022

3

 

 

 

 

 

 

 

28/10/2022

3

 

 

 

 

 

 

 

29/10/2022

3

 

 

 

 

 

 

 

30/10/2022

3

 

 

 

 

 

 

 

31/10/2022

3

 

 

 

 

 

 

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.
* - Unit L10 was not on load.

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L11 (Operation)

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

1/10/2022

3

 

 

 

 

 

 

 

2/10/2022

*

 

 

 

 

 

 

 

3/10/2022

2

 

 

 

 

 

 

 

4/10/2022

3

 

 

 

 

 

 

 

5/10/2022

2

 

 

 

 

 

 

 

6/10/2022

2

 

 

 

 

 

 

 

7/10/2022

2

 

 

 

 

 

 

 

8/10/2022

3

 

 

 

 

 

 

 

9/10/2022

2

 

 

 

 

 

 

 

10/10/2022

3

 

 

 

 

 

 

 

11/10/2022

3

 

 

 

 

 

 

 

12/10/2022

3

 

 

 

 

 

 

 

13/10/2022

3

 

 

 

 

 

 

 

14/10/2022

3

 

 

 

 

 

 

 

15/10/2022

3

 

 

 

 

 

 

 

16/10/2022

3

 

 

 

 

 

 

 

17/10/2022

2

 

 

 

 

 

 

 

18/10/2022

3

 

 

 

 

 

 

 

19/10/2022

3

 

 

 

 

 

 

 

20/10/2022

2

 

 

 

 

 

 

 

21/10/2022

2

 

 

 

 

 

 

 

22/10/2022

2

 

 

 

 

 

 

 

23/10/2022

2

24/10/2022

2

25/10/2022

3

26/10/2022

3

27/10/2022

3

 

 

 

 

 

 

 

28/10/2022

3

29/10/2022

3

30/10/2022

3

 

 

 

 

 

 

 

31/10/2022

3

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L11 was not on load.