Lamma Power Station Extension - Air Quality Monitoring Data for unit L13 (Construction)

 

24-hr TSP (µg/m3)

1-hr TSP (µg/m3)

 

Date

Reservoir

 (AM1)

East Gate

 (AM2)

Ash Lagoon (AM3)

Tai Yuen Village (AM4)

Date

Time

Reservoir (AM1)

East Gate (AM2)

Ash Lagoon (AM3)

 

3/4/2025

45

53

47

7

3/4/2025

15:00 - 15:59

49

140

43

 

9/4/2025

46

42

35

14

16:00 - 16:59

48

147

41

 

15/4/2025

249^

256^

205^

163

17:00 - 17:59

44

57

37

 

21/4/2025

36

22

18

25

9/4/2025

15:00 - 15:59

28

29

27

 

27/4/2025

26

23

22

31

16:00 - 16:59

24

32

26

 

 

 

 

 

 

17:00 - 17:59

26

33

25

 

 

^ -  Action level exceedances of 24-hour TSP were recorded at AM1 to AM3 on 15 April 2025.  According to the information from EPD, the high dust episode was due to the influence of a dusty air stream associated with the northeast monsoon and all EPD monitoring stations also recorded daily AQO exceedance for RSP.  As such, we are of the view that the 24-hour action level exceedances are non-project related.

 

 

16/4/2025

15:00 - 15:59

226

228

177

 

16:00 - 16:59

220

231

195

 

17:00 - 17:59

266

243

219

 

 

21/4/2025

15:00 - 15:59

27

20

17

 

 

16:00 - 16:59

87

21

17

 

 

17:00 - 17:59

124

20

15

 

 

27/4/2025

15:00 - 15:59

23

22

21

 

 

16:00 - 16:59

21

21

21

 

 

 

 

 

 

 

17:00 - 17:59

22

21

22

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L9 (Operation)

 

 

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

 

1/4/2025

77

 

2/4/2025

77

 

3/4/2025

81

 

4/4/2025

*

 

5/4/2025

*

 

6/4/2025

*

 

7/4/2025

80

 

8/4/2025

77

 

9/4/2025

73

 

10/4/2025

79

 

11/4/2025

79

 

12/4/2025

79

 

13/4/2025

*

 

14/4/2025

78

 

15/4/2025

76

 

16/4/2025

72

 

17/4/2025

70

 

18/4/2025

*

 

19/4/2025

75

 

20/4/2025

75

 

21/4/2025

74

 

22/4/2025

71

 

23/4/2025

72

 

24/4/2025

76

 

25/4/2025

78

 

26/4/2025

78

 

 

 

 

 

 

 

 

27/4/2025

79

 

 

 

 

 

 

 

 

28/4/2025

74

 

 

 

 

 

 

 

 

29/4/2025

78

 

 

 

 

 

 

 

 

30/4/2025

79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

^ - The NOx concentration exceeded action level due to low relative humidity.

 

 

 

 

 

* - Unit L9 was not on load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L10 (Operation)

 

 

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

 

1/4/2025

*

 

2/4/2025

*

 

3/4/2025

*

 

4/4/2025

*

 

5/4/2025

*

 

6/4/2025

4

 

7/4/2025

3

 

8/4/2025

8^

 

9/4/2025

3

 

10/4/2025

3

 

11/4/2025

3

 

12/4/2025

3

 

13/4/2025

3

 

14/4/2025

3

 

15/4/2025

3

 

16/4/2025

4

 

17/4/2025

3

 

18/4/2025

3

 

19/4/2025

3

 

20/4/2025

3

 

21/4/2025

3

 

22/4/2025

3

 

23/4/2025

3

 

24/4/2025

3

 

25/4/2025

3

 

26/4/2025

3

 

 

 

 

 

 

 

 

27/4/2025

3

 

 

 

 

 

 

 

 

28/4/2025

3

 

 

 

 

 

 

 

 

29/4/2025

3

 

 

 

 

 

 

 

 

30/4/2025

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L10 was not on load.

^ - Unit L10 was operating with loading less than 266 MW.

 

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L11 (Operation)

 

 

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

 

1/4/2025

7^

 

2/4/2025

5^

 

3/4/2025

5^

 

4/4/2025

5^

 

5/4/2025

4^

 

 

 

 

 

 

 

 

6/4/2025

4^

 

 

 

 

 

 

 

 

7/4/2025

*

 

8/4/2025

*

 

9/4/2025

*

 

10/4/2025

*

 

11/4/2025

*

 

12/4/2025

*

 

 

 

 

 

 

 

 

13/4/2025

*

 

 

 

 

 

 

 

 

14/4/2025

*

 

 

 

 

 

 

 

 

15/4/2025

*

 

 

 

 

 

 

 

 

16/4/2025

*

 

 

 

 

 

 

 

 

17/4/2025

*

 

 

 

 

 

 

 

 

18/4/2025

*

 

 

 

 

 

 

 

 

19/4/2025

*

 

 

 

 

 

 

 

 

20/4/2025

*

 

 

 

 

 

 

 

 

21/4/2025

*

 

 

 

 

 

 

 

 

22/4/2025

*

 

 

 

 

 

 

 

 

23/4/2025

*

 

 

 

 

 

 

 

 

24/4/2025

*

 

 

 

 

 

 

 

 

25/4/2025

*

 

 

 

 

 

 

 

 

26/4/2025

*

 

 

 

 

 

 

 

 

27/4/2025

*

 

 

 

 

 

 

 

 

28/4/2025

*

 

 

 

 

 

 

 

 

29/4/2025

*

 

 

 

 

 

 

 

 

30/4/2025

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L11 was not on load.

^ - Unit L11 was operating with loading less than 266 MW.

 

 

 

Lamma Power Station Extension - Air Quality Monitoring Data for unit L12 (Operation)

 

 

 

Date

Daily Maximum Stack NOx concentration (mg/Nm3)#

 

1/4/2025

4

 

2/4/2025

4

 

3/4/2025

4

 

4/4/2025

4

 

 

 

 

 

 

 

 

5/4/2025

4

 

6/4/2025

4

 

 

 

 

 

 

 

 

7/4/2025

4

 

8/4/2025

4

 

9/4/2025

4

 

10/4/2025

4

 

11/4/2025

4

 

12/4/2025

3

 

 

 

 

 

 

 

 

13/4/2025

4

 

 

 

 

 

 

 

 

14/4/2025

4

 

 

 

 

 

 

 

 

15/4/2025

4

 

 

 

 

 

 

 

 

16/4/2025

4

 

 

 

 

 

 

 

 

17/4/2025

4

 

 

 

 

 

 

 

 

18/4/2025

4

 

 

 

 

 

 

 

 

19/4/2025

4

 

 

 

 

 

 

 

 

20/4/2025

3

 

 

 

 

 

 

 

 

21/4/2025

3

 

 

 

 

 

 

 

 

22/4/2025

4

 

 

 

 

 

 

 

 

23/4/2025

4

 

 

 

 

 

 

 

 

24/4/2025

4

 

 

 

 

 

 

 

 

25/4/2025

4

 

 

 

 

 

 

 

 

26/4/2025

4

 

 

 

 

 

 

 

 

27/4/2025

5^

 

 

 

 

 

 

 

 

28/4/2025

4

 

 

 

 

 

 

 

 

29/4/2025

5^

 

 

 

 

 

 

 

 

30/4/2025

5^

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The daily maximum stack NOx concentration complies with the Action/Limit Level for all unit loading ranges.

 

Note:

# - Hourly average value.  Expressed as at 0¢XC, 101.325kPa, dry and corrected to 15% O2 condition.

* - Unit L12 was not on load.

^ - Unit L12 was operating with loading less than 266 MW.