APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: March 2002

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

06/03/2002

161

155

125

93

33.5

010

47

12/03/2002

49

51

63

85

16.3

060

84

18/03/2002

64

70

68

82

26.3

080

73

24/03/2002

32

36

53

22

26.7

050

95

30/03/2002

70

72

82

57

10.5

080

93

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

06/03/2002

15:00-15:59

118

104

104

16:00-16:59

140

139

140

17:00-17:59

187

181

181

12/03/2002

15:00-15:59

43

47

49

16:00-16:59

58

56

58

17:00-17:59

74

63

69

18/03/2002

15:00-15:59

37

52

50

16:00-16:59

57

67

62

17:00-17:59

62

61

59

24/03/2002

15:00-15:59

98

91

95

16:00-16:59

36

34

29

17:00-17:59

23

28

20

30/03/2002

15:00-15:59

91

91

94

16:00-16:59

103

98

105

17:00-17:59

91

93

87

Remark:

(1)                 The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

 

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

Calibration:            Calibration details are shown in appendix G.

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler