APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: April 2002

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

05/04/2002

91

26

25

33

22.3

190

79

11/04/2002

72

71

(2)

36

26.5

360

80

13/04/2002

-

-

45

-

17.3

070

73

17/04/2002

36

38

31

26

7.6

120

83

23/04/2002

19

26

20

28

11.8

090

81

29/04/2002

35

32

32

46

19.9

060

85

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

05/04/2002

15:00-15:59

37

33

31

16:00-16:59

30

21

19

17:00-17:59

25

25

20

11/04/2002

15:00-15:59

81

72

70

16:00-16:59

92

91

85

17:00-17:59

92

120

86

17/04/2002

15:00-15:59

24

44

27

16:00-16:59

17

25

31

17:00-17:59

73

69

44

23/04/2002

15:00-15:59

10

12

14

16:00-16:59

7

19

14

17:00-17:59

43

27

29

29/04/2002

15:00-15:59

30

31

32

16:00-16:59

52

34

32

17:00-17:59

35

34

33

Remark:

(1)                 The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)                 Partisol TSP sampler at AM3 (Ash Lagoon) was found defective during the collection of filter paper on 12/4/2002.  The defect was rectified on the same day.  A make-up 24hr TSP sampling for AM3 was carried out on 13/4/2002.

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

Calibration:            Calibration details are shown in appendix G.

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler