APPENDIX D  AIR QUALITY MONITORING RESULTS
 
Site: Lamma Power
Station Extension
 
Month: May 2002
 
24 hour TSP
Measurement:-
| Date | TSP concentration (mg/m3) | Weather Information (From Hong Kong Observatory) | |||||
| Reservoir   (AM1) | East Gate (AM2) | Ash Lagoon   (AM3) | Tai Yuen Village (AM4) | Mean Wind Speed (km/hr) | Prevailing Wind Dir. (°) | Mean R.H.   (%) | |
| 05/05/2002 | 32  | 35  | 30  | 47  | 24.5 | 090 | 79 | 
| 11/05/2002 | 69  | 50  | 44  | 64  | 9.4 | 220 | 79 | 
| 17/05/2002 | 20  | 19  | 17  | 25  | 16.9 | 060 | 89 | 
| 23/05/2002 | 78  | 84  | 61  | 60  | 15.1 | 010 | 80 | 
| 29/05/2002 | 40  | 38  | 38  | 43  | 14.4 | 050 | 77 | 
 
1 hour TSP Measurement:-
| Date | Time | TSP concentration (mg/m3) | ||
| Reservoir (AM1) | East Gate (AM2) | Ash Lagoon (AM3) | ||
| 05/05/2002 | 15:00-15:59 | 31 | 33 | 31 | 
| 16:00-16:59 | 31 | 37 | 29 | |
| 17:00-17:59 | 37 | 42 | 36 | |
| 11/05/2002 | 15:00-15:59 | 57 | 44 | 41 | 
| 16:00-16:59 | 91 | 98 | 89 | |
| 17:00-17:59 | 117 | 119 | 113 | |
| 17/05/2002 | 15:00-15:59 | 62 | 29 | 24 | 
| 16:00-16:59 | 23 | 23 | 19 | |
| 17:00-17:59 | 21 | 20 | 23 | |
| 23/05/2002 | 15:00-15:59 | 136 | 135 | 133 | 
| 16:00-16:59 | 76 | 76 | 78 | |
| 17:00-17:59 | 37 | 47 | 45 | |
| 29/05/2002 | 15:00-15:59 | 26 | 27 | 21 | 
| 16:00-16:59 | 28 | 24 | 27 | |
| 17:00-17:59 | 25 | 26 | 28 | |
Remark:
(1)                
The monitoring stations, Reservoir, East Gate
& Ash Lagoon are located within Lamma Power Station.
 
 
                                                                        1-hr
TSP                24-hr
TSP
                                                                          (mg/m3)                   (mg/m3)
Action Level                                                      340                          190
Limit Level                                                          500                          260
 
Calibration:            Calibration
details are shown in appendix G.
 
Equipment used:
| Location | 1-hr TSP | 24-hr TSP | 
| Reservoir and East Gate | TEOM 1400a | High Volume Air Sampler | 
| Ash Lagoon | Partisol Model 2000 Sampler | |
| Tai Yuen Village | - | MINIVOL Portable Sampler | 

 
 

 
 
 

 
 