APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: February 2003

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

05/02/2003

66

58

60

56

26.0

010

60

11/02/2003

63

53

54

54

23.2

040

85

17/02/2003

(2)

33

35

31

28.8

060

88

19/02/2003

54

-

-

-

11.9

040

85

23/02/2003

38

40

40

40

3.9

220

82

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

05/02/2003

15:00-15:59

60

66

72

16:00-16:59

64

68

67

17:00-17:59

63

63

68

11/02/2003

15:00-15:59

62

52

48

16:00-16:59

61

61

57

17:00-17:59

58

49

52

17/02/2003

15:00-15:59

31

31

33

16:00-16:59

29

28

31

17:00-17:59

31

29

32

23/02/2003

15:00-15:59

32

37

42

16:00-16:59

38

34

36

17:00-17:59

37

34

35

Remark:

(1)                 The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)                 High Volume Air Sampler (HVAS) at AM1 (Reservoir) was found defective during the collection of filter paper on 18/02/2003. The defect was rectified on the same day.  A 24 hour TSP make-up sampling was performed on 19/02/2003.

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

Calibration:            Calibration details are shown in appendix F.

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler