APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: March 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

01/03/2004

32

50

30

42

17.9

180

83

07/03/2004

146

146

145

157

44.4

070

63

13/03/2004

50

50

50

67

28.8

070

87

19/03/2004

61

59

52

61

33.8

070

75

25/03/2004

25

24

21

28

26.6

050

96

31/03/2004

69

65

65

71

28.4

090

92

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

01/03/2004

15:00-15:59

30

43

24

16:00-16:59

29

57

25

17:00-17:59

29

33

28

07/03/2004

15:00-15:59

137

123

146

16:00-16:59

139

132

153

17:00-17:59

130

123

137

13/03/2004

15:00-15:59

58

57

60

16:00-16:59

52

48

54

17:00-17:59

51

51

48

19/03/2004

15:00-15:59

61

58

60

16:00-16:59

58

56

63

17:00-17:59

61

57

63

25/03/2004

15:00-15:59

30

20

21

16:00-16:59

35

31

29

17:00-17:59

17

21

19

31/03/2004

15:00-15:59

65

65

68

16:00-16:59

61

62

62

17:00-17:59

58

55

57

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

 

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

Calibration:            Calibration details are shown in appendix F.

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler