APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: May 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

04/05/2004

98(2)

-

-

-

14.1

020

83

06/05/2004

52

48

49

47

21.3

090

82

12/05/2004

24

21

17

19

10.7

190

81

18/05/2004

58

53

57

67

13.9

060

82

24/05/2004

58

53

51

49

26.0

090

73

30/05/2004

23

38

16

19

14.4

180

81

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

06/05/2004

15:00-15:59

55

56

57

16:00-16:59

46

43

48

17:00-17:59

40

41

42

12/05/2004

15:00-15:59

20

92

8

16:00-16:59

13

13

5

17:00-17:59

17

17

11

18/05/2004

15:00-15:59

64

60

61

16:00-16:59

64

61

61

17:00-17:59

60

53

56

24/05/2004

15:00-15:59

87

70

84

16:00-16:59

69

60

68

17:00-17:59

71

66

66

30/05/2004

15:00-15:59

18

20

22

16:00-16:59

24

20

26

17:00-17:59

19

22

20

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)        Make up sampling for the dust sampling at Reservoir Area originally scheduled on 30/4/2004 due to the malfunction of HVAS.

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

Calibration:            Calibration details are shown in appendix F.

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler