APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: August 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

04/08/2004

28

42

17

24

13.5

240

78

10/08/2004

84

99

79

78

9.7

260

72

16/08/2004

25

53

24

15

8.6

130

75

22/08/2004

15

65

31

22

12.6

050

93

28/08/2004

28

(2)

23

13

22.5

170

92

31/08/2004

-

42

-

-

17.5

210

88

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

04/08/2004

15:00-15:59

28

47

30

16:00-16:59

37

36

27

17:00-17:59

32

28

21

10/08/2004

15:00-15:59

128

135

108

16:00-16:59

163

170

137

17:00-17:59

114

128

87

16/08/2004

15:00-15:59

24

65

24

16:00-16:59

37

56

30

17:00-17:59

52

23

26

22/08/2004

15:00-15:59

6

13

1

16:00-16:59

16

19

18

17:00-17:59

0

12

7

28/08/2004

15:00-15:59

2

37

13

16:00-16:59

0

25

0

17:00-17:59

12

37

15

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)            24-hr TSP sampling at AM2 (East Gate) was found defective during the collection of filter paper on 30/8/2004. Defect was rectified on the same day.  Make-up TSP sampling at AM2 was conducted on 31/08/2004.

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

Calibration:            Calibration details are shown in appendix F.

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler