APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: September 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

03/09/2004

17

20

(2)

18

14.9

110

91

04/09/2004

-

-

22

-

6.7

160

81

09/09/2004

48

55

50

43

11.5

310

90

15/09/2004

146

130

144

172

7.1

200

63

21/09/2004

36

54

27

24

12.5

240

80

27/09/2004

105

102

92

86

10.0

010

59

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

03/09/2004

15:00-15:59

26

5

6

16:00-16:59

27

14

10

17:00-17:59

11

0

9

09/09/2004

15:00-15:59

64

77

82

16:00-16:59

69

80

87

17:00-17:59

63

86

71

15/09/2004

15:00-15:59

243

212

217

16:00-16:59

162

166

162

17:00-17:59

174

124

144

21/09/2004

15:00-15:59

31

41

22

16:00-16:59

26

49

29

17:00-17:59

27

84

27

27/09/2004

15:00-15:59

84

91

82

16:00-16:59

87

92

79

17:00-17:59

93

76

85

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)        24-hr TSP sampling at AM3 (Ash Lagoon) was found defective.  MiniVol TSP sampler is used to temporarily replace the defective Partisol TSP sampler which was taken out of service for repair.  Make-up TSP sampling at AM3 was conducted on 04/09/2004.  Partisol TSP sampler was repaired and put back into service on 21/09/2004.

 

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

Calibration:            Calibration details are shown in appendix F.

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler /

MINIVOL Portable sampler

Tai Yuen Village

-

MINIVOL Portable Sampler