APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: October 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

03/10/2004

107

84

77

92

42.5

010

50

09/10/2004

101

93

95

104

18.8

020

54

15/10/2004

84

83

84

97

33.2

090

67

21/10/2004

91

83

96

108

23.5

090

73

27/10/2004

101

88

101

97

34.0

090

66

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

03/10/2004

15:00-15:59

65

77

76

16:00-16:59

69

163

112

17:00-17:59

45

96

107

09/10/2004

15:00-15:59

112

105

118

16:00-16:59

122

123

126

17:00-17:59

109

100

117

15/10/2004

15:00-15:59

75

70

80

16:00-16:59

72

62

78

17:00-17:59

91

80

92

21/10/2004

15:00-15:59

87

85

90

16:00-16:59

91

75

99

17:00-17:59

104

98

104

27/10/2004

15:00-15:59

124

103

125

16:00-16:59

101

88

96

17:00-17:59

102

82

109

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

Calibration:            Calibration details are shown in appendix F.

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler /

MINIVOL Portable sampler

Tai Yuen Village

-

MINIVOL Portable Sampler