APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: December 2004

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

02/12/2004

70

57

71

54

26.1

050

76

08/12/2004

141

120

105

99

21.2

010

55

14/12/2004

79

65

73

64

29.3

070

72

20/12/2004

95

72

78

81

17.6

090

81

26/12/2004

(1)

40

43

60

28.8

090

78

30/12/2004

158

-

-

-

33.9

010

68

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

02/12/2004

15:00-15:59

71

58

71

16:00-16:59

71

61

73

17:00-17:59

73

65

76

08/12/2004

15:00-15:59

91

98

96

16:00-16:59

88

87

90

17:00-17:59

87

72

91

14/12/2004

15:00-15:59

61

61

58

16:00-16:59

59

50

58

17:00-17:59

59

55

63

20/12/2004

15:00-15:59

87

90

53

16:00-16:59

79

69

54

17:00-17:59

86

81

60

26/12/2004

15:00-15:59

39

39

40

16:00-16:59

51

47

46

17:00-17:59

46

43

48

 

Remark:

(1)            The monitoring stations, Reservoir, East Gate & Ash Lagoon are located within Lamma Power Station.

(2)            HVAS 24-hr TSP sampler at AM1 (Reservoir) was found defective on 28/12/2004, during the collection of filter sample.  Defect was rectified on 29/12/2004.  A make-up 24-hr TSP sampling for AM1 was carried out on 30/12/2004.                                                                             

 

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

 

Calibration:            Calibration details are shown in appendix F.

 

 

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler