APPENDIX D  AIR QUALITY MONITORING RESULTS

 

Site: Lamma Power Station Extension

 

Month: September 2006

 

24 hour TSP Measurement:-

Date

TSP concentration (mg/m3)

Weather Information

(From Hong Kong Observatory)

Reservoir

 

(AM1)

East

Gate

(AM2)

Ash Lagoon

 

(AM3)

Tai Yuen Village

(AM4)

Mean Wind Speed

(km/hr)

Prevailing Wind Dir.

(°)

Mean R.H.

 

(%)

05/09/2006

27

43

22

21

25.0

240

78

11/09/2006

59

55

65

38

36.5

010

74

17/09/2006

87

66

74

56

24.5

010

64

23/09/2006

63

57

72

78

44.0

080

68

29/09/2006

50

48

54

90

32.6

080

73

 

1 hour TSP Measurement:-

Date

Time

TSP concentration (mg/m3)

Reservoir

(AM1)

East Gate

(AM2)

Ash Lagoon

(AM3)

05/09/2006

15:00-15:59

18

21

10

16:00-16:59

17

38

15

17:00-17:59

18

36

16

11/09/2006

15:00-15:59

73

74

75

16:00-16:59

53

50

58

17:00-17:59

43

39

43

17/09/2006

15:00-15:59

118

101

95

16:00-16:59

104

73

79

17:00-17:59

86

89

63

23/09/2006

15:00-15:59

93

77

80

16:00-16:59

67

56

60

17:00-17:59

55

48

53

29/09/2006

15:00-15:59

69

53

64

16:00-16:59

81

65

74

17:00-17:59

77

64

72

 

 

                                                                        1-hr TSP                24-hr TSP

                                                                          (mg/m3)                   (mg/m3)

Action Level                                                      340                          190

Limit Level                                                          500                          260

 

 

 

Calibration:            Calibration details are shown in appendix F.

 

 

 

 

Equipment used:

Location

1-hr TSP

24-hr TSP

Reservoir and East Gate

TEOM 1400a

High Volume Air Sampler

Ash Lagoon

Partisol Model 2000 Sampler

Tai Yuen Village

-

MINIVOL Portable Sampler